GTM961200P120VV.V-P2 Potted/Encapsulated in plastic housing ICT / ITE / Medical Power Supply

GTM961200P120VV.V-P2
GTM961200P120VV.V-P2, ICT / ITE / Medical Power Supply, Potted/Encapsulated in plastic housing, Regulated Switchmode AC-DC Power Supply AC Adaptor, , Input Rating: 100-240V~, 50-60 Hz, See \GTM961200P120VV.V-P2, ICT / ITE / Medical Power Supply, Potted/Encapsulated in plastic housing, Regulated Switchmode AC-DC Power Supply AC Adaptor, , Input Rating: 100-240V~, 50-60 Hz, See "Blade/Cord Installed" section. Contact GlobTek for customization requests such as Molded country plugs, Molex or TE connectors, or IEC connectors mounted on any type of cable in any customer specified lengths., Output Rating: 120 Watts, Power rating with convection cooling (W) , 12-54V in 0.1V increments, Approvals: IP68; CB 61347; CB 62368; PSE; PSE; PSE; PSE; S-Mark 62368; IRAM; UKCA; Conforms to 62368-1; S-Mark; Morocco;
Information
Model NumberGTM961200P120VV.V-P2
Agency Documentshttp://www.globtek.info/certs/GTM961200P/
CE EC-Declaration for MedicalContact GlobTek for more information
CE EC-Declaration for Industrial/Commercial/ITEhttps://cs.globtek.info/ec_declaration?id=a0O0c00000PzQxxEAF
CE EC-Declaration for HouseholdContact GlobTek for more information
UKCA-Declaration for MedicalContact GlobTek for more information
UKCA-Declaration for Industrial/Commercial/ITEhttps://cs.globtek.info/ukca_declaration?id=a0O0c00000PzQxxEAF
UKCA-Declaration for HouseholdContact GlobTek for more information
Morocco SDoC Declarationhttps://cs.globtek.info/Morocco_SDoC_Declaration?id=a0O0c00000PzQxxEAF
RoHS/RoHS3 Declarationhttps://www.globtek.com/pdf/rohs_cert/a0O0c00000PzQxxEAF
Prop 65 Statementhttps://www.globtek.com/r2/PH7CNf
REACH Declarationhttps://www.globtek.com/r2/eM2co8
Conflict Minerals Declarationhttps://www.globtek.com/r2/vZY8R5
Model Parameters
TypePotted/Encapsulated in plastic housing
TechnologyRegulated Switchmode AC-DC Power Supply AC Adaptor
CategoryICT / ITE / Medical Power Supply
Input Voltage Range (V)100-240V~, 50-60 Hz
Max Input Current (A)0
Max Output Power Rating (W)120
Output Voltage Range (V)12-54
EfficiencyUSA DOE Level VI / Eco-design Directive 2009/125/EC, (EU) 2019/1782
Ingress ProtectionIP68
Size (mm)178.0*76.0*39.5 +/- 1.0 mm
Enclosure

User-added image


 
3D File Downloadhttps://www.globtek.com/file/dl/GTM961200PWWWVV.V-P2.zip
Rating Table
Model Number (Final ordering #/Part No to be defined)Voltage (V)Current (A)Power (W)RFQ
* (Final ordering #/Part No to be defined)
Specifications
A) ELECTRICAL SPECIFICATIONS:
01. Input Voltage: Specified 90-264 Vac, Nameplate rated: 100-240Vac
         90-264Vac range @ 100% of rated load current
         85-264 Vac range @ 90% of rated load current
         90-370 VDC range @ 100% of rated load current
02. Input Frequency: Specified 47-63 Hz, Nameplate rated 50/60Hz
03. Power Factor: 0.90 minimum @ 230Vac, 0.97 minimum @ 115Vac
04. Output Regulation: +/- 4% measured at the output connector
05. Line Voltage Regulation: +/- 0.5% typical measured at full load
06. Green Power On Indicator LED
07. Output Ripple (Vp-p): 1% or 200 mV whichever is greater, measured at 20 MHz bandwidth with 0.1 uf ceramic capacitor in parallel with a low impedance 47 uf electrolytic capacitor connected at the end of the output connector at nominal line
08. Turn-ON/OFF Overshoot: 8% maximum, 1 mS typical recovery time for 25% to 50% step load
09. Turn-ON Delay: 1 second typical
10. Hold-Up Time: 20 mS minimum
11. Inrush Current: 30A maximum at 115Vac input and 60A maximum at 230 Vac input
12. Switching Frequency: Varies from 25KHz to 125KHz
13. Efficiency: Compliant with Efficiency Level VI standard and 230 CoC Tier 2 Limits
14. No Load Standby Power: <0.15 W @ 230Vac

B) PROTECTION
01. Input Protection: Input line fusing and 300Vac rated MOV
02. Short Circuit/ Overload: Electronically Protected unit will auto recover upon removal of fault
         Output Current Limit: Current limited to less than 170W / Vnom and 13A
         (Vnom = nominal rated output voltage)
03. Over-Temperature : Latching Electronic Overtemperature protection. Cycle AC OFF to reset.
04. Output Over-Voltage: 110% to 135% of nominal output voltage under full load condition, and less than 60V max. Latching protection, cycle AC OFF to reset.

C) SAFETY
01. Dielectric Withstand Voltage: 4000Vac or 5656Vdc from input to output,
On Class I models, 3000Vac or 4242Vdc from input to earth
02. Earth Leakage Current: Class I models < 300uA, N/A for Class II models
03. Touch Current: Class I models < 20uA, Class II models < 70uA
04. Output Isolation Options:
   a) C8 or C18 Inlet, Class II
   b) C6 or C14 Inlet, Class II FE, Output Isolated from Earth contact
   c) C6 or C14 Inlet,  Class I, Output negative directly attached to Earth contact
05. Earth Continuity Test: < 0.1 Ohm between Earth Pin at AC input and PCB termination point (Class I models only)
06. Means of Protection: 2 x MOPP
07. Primary to Secondary Bridging Capacitance: Two IEC60384-14 certified Y1 type capacitors in series
08. Compliant Standards: See listings at end of this drawing for specifics

D) EMC
EN 60601-1-2, 4th edition
Emissions, per EN 55032, EN 61000-6-3, EN 61000-6-4
  Conducted Emissions: Class B, FCC Part 15, Class B
  Radiated Emissions: Class B, FCC Part 15, Class B
Line Frequency Harmonics EN61000-3-2, Class A
Voltage Fluctuations/Flicker EN61000-3-3
 
Immunity, per EN 55024, EN 61000-6-1, EN 61000-6-2
  Static Discharge Immunity EN61000-4-2, 10kV Contact Discharge, 18kV air discharge
  Radiated RF Immunity EN61000-4-3, 10V/m 80-1000MHz, 3V/m 1-2.7GHz, 80% 1KHz AM.
  EFT/Burst Immunity EN61000-4-4, 4kV/100kHz.
  Line Surge Immunity EN61000-4-5, 2kV differential, 4kV common-mode
  Conducted RF Immunity EN61000-4-6, 3Vrms, 80% 1KHz AM
  Power Frequency Magnetic Field Immunity EN61000-4-8, 3A/m
  Voltage Dip Immunity EN61000-4-11, Criteria

E) OTHER:
01. MTBF: 500,000 Hours @ 40°C ambient temperature, Full Load
02. Operating Temperature:
    GTM961200P Family: -20°C to 40°C ambient temperature with full load
    Regarding Operating Temperature, 
    a- See below derating table for output power capability at alternate temperature
    b- Extended low end temperature range available as custom option
03. Humidity: 0% to 95% relative humidity, non-condensing
04. Storage Temperature: -30°C to 80°C
05. Cooling: Convection
06. ROHS: Compliant with latest regulations, see approvals section below
07. Operational Altitude: 5000M

F) ENCLOSURE
01. Markings: Label or Laser printed

G) SPECIAL OPTIONS
01. Custom Cordsets, various cordage types, and connector types
02. Custom Markings
03. Short term Output Surge Capability
04. Reduced Leakage Current version, medical CF leakage current compliance
05. Tightened output voltage tolerance
06. Reduced Output Ripple Level
07. LED Lighting, Class C Line Harmonics per 61000-3-2, from 85W to 120W output
08. Reduced output power marking/rating
09. High Rel PCB laminate with Plated through Holes for IPC610 Class 2 Compliance
10. Low Temperature operation, down to -40°C
11. Special Housing Colors and Cordset Colors

H) OUTPUT CONNECTORS
Several output connector options are available with various output current ratings.
GlobTek can supply 10A rated 2.1mm and 2.5mm style DC Power Jacks, to complement our
10A output rated 2.1mm and 2.5mm DC power plugs used on our output cordsets.
      2.1mm PCB DC Power Jack ordering code: JACK-C-PC-10A-RA(R)  
      2.5mm PCB DC Power Jack ordering code: JACK-L-PC-10A-RA(R)
Derating CurveUser-added image
Qty (ea.)/Carton
Individual Box/Gift Box Size (mm)
Individual Box/Gift Box Color
Master Carton Size (mm)TBD
Gross Weight (kg)
Label Width (mm)119 +2,-0.2
Label Height (mm)59 +2,-0.2
Input Configuration
DescriptionSee "Blade/Cord Installed" section. Contact GlobTek for customization requests such as Molded country plugs, Molex or TE connectors, or IEC connectors mounted on any type of cable in any customer specified lengths.
Output Configuration
Common output connector options:
Click to add to your request.
L Type (Coaxial 5.5x2.5mm plug)
C Type (Coaxial 5.5x2.1mm plug)
K Type (Coaxial 3.5x1.3mm plug)
LL Type (5.5x2.5mm Locking 760k type)
CL Type (5.5x2.1mm Locking S761k type)
Magnetic Connector
L Type (Coaxial 5.5x2.5mm plug)C Type (Coaxial 5.5x2.1mm plug)K Type (Coaxial 3.5x1.3mm plug)LL Type (5.5x2.5mm Locking 760k type)CL Type (5.5x2.1mm Locking S761k type)Magnetic Connector
YL3 Type (KPPX-3P)
YL4 Type (KPPX-4P)
EJ1/2/3/4/5 (EIAJ RC-5320A type connectors)
MSB Type (Micro USB)
Custom design
YL3 Type (KPPX-3P)YL4 Type (KPPX-4P)EJ1/2/3/4/5 (EIAJ RC-5320A type connectors)MSB Type (Micro USB)Inquire for custom design

Comprehensive list of GlobTek output cordset options

Contact GlobTek for your specific requirements or custom solutions.

Approvals

Below follows a link to the latest regulatory certifications and marks for this specific product. National standards as well as certification schemes are constantly changing and so is the set of certification marks and symbols applicable to this product. Various standards, marks and symbols, and certificates are subject to change at any time without notice.

Additional standards or unique country certifications are available upon request. Please contact Globtek to request a quotation.

LogoDescription

No Logo Applicable

CB for IEC61347-1:2015 + A1:2017 IEC61347-2-13:2014, A1:2016
User-added imageJAPAN TUV R-PSE, Cert. No. JD 50469658, to J62368-1(H30) , J55032(H29),J3000(H25)[15V or less]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
User-added image
PRECAUCION: PARA USO EN EQUIPOS ELECTRONICOS SOLAMENTE
 
IRAM certificateDC-E-G71-005.1 to IEC 62368-1:2014
IP68Ingress Protection: ?IP68 to IEC60529:2001 Totally dust tight and Protected against long periods of immersion under pressure
User-added image
 
S-Mark Certificate EN 62368-1:2014 + A11 (http://www.intertek.com/marks/s/)
User-added imageUKCA Certification
User-added imageJAPAN TUV R-PSE, Cert. No. JD 50469658, to J62368-1(H30) , J55032(H29),J3000(H25)[DC15?30V]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
User-added imageJAPAN TUV R-PSE, Cert. No. JD 50469658, to J62368-1(H30) , J55032(H29),J3000(H25)[DC30?60V]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
User-added image
 
S-Mark Certificate EN 60601-1:2006 + A1:2013 + A12:2014 EN 60601-1-11:2015 (http://www.intertek.com/marks/s/)

No Logo Applicable

CB for IEC 62368-1:2014 (Second Edition)
User-added imageJAPAN TUV R-PSE, Cert. No. JD 50469658, to J62368-1(H30) , J55032(H29),J3000(H25)[DC15?30V]. Please reference the following website for guidelines on PSE regulations: https://www.globtek.com/r2/Szj4Vb
User-added image
 
Morocco SDoC declaration http://www.globtek.info/certs/Morocco%20SDoC%20Declaration/
Conforms to UL STD. 62368-1
Certified to CSA STD C22.2 NO.62368-1
Conforms to UL STD. 62368-1 Certified to CSA STD C22.2 NO.62368-1
Request Info