GT-G3062P800VV-X.X-C Enclosed-Metal ICT/ITE Power Supply

GT-G3062P800VV-X.X-C
GT-G3062P800VV-X.X-C, ICT/ITE Power Supply, Enclosed-Metal, Programmable Single Output Power Supply AC Adaptor, , Input Rating: 90 ~ 264VAC, 127 ~ 370VDC (47 ~ 63Hz), 3 Positon Terminal Block, Output Rating: 800 Watts, Power rating with convection cooling (W) , 12-60V in 0.1V increments, Approvals: China RoHS; Class I; cULus; PSE; RoHS; VCCI; WEEE; CE; GOST-R; Ukraine;GT-G3062P800VV-X.X-C, ICT/ITE Power Supply, Enclosed-Metal, Programmable Single Output Power Supply AC Adaptor, , Input Rating: 90 ~ 264VAC, 127 ~ 370VDC (47 ~ 63Hz), 3 Positon Terminal Block, Output Rating: 800 Watts, Power rating with convection cooling (W) , 12-60V in 0.1V increments, Approvals: China RoHS; Class I; cULus; PSE; RoHS; VCCI; WEEE; CE; GOST-R; Ukraine;
Information
Model NumberGT-G3062P800VV-X.X-C
Agency Documentshttp://www.globtek.info/certs/GT-G3062PWWWVV-X.X-C/
CE EC-Declaration for MedicalContact GlobTek for more information
CE EC-Declaration for Industrial/Commercial/ITEhttps://cs.globtek.info/ec_declaration?id=a0Oa000000MiWjWEAV
CE EC-Declaration for HouseholdContact GlobTek for more information
UKCA-Declaration for MedicalContact GlobTek for more information
UKCA-Declaration for Industrial/Commercial/ITEhttps://cs.globtek.info/ukca_declaration?id=a0Oa000000MiWjWEAV
UKCA-Declaration for HouseholdContact GlobTek for more information
Morocco SDoC Declarationhttps://cs.globtek.info/Morocco_SDoC_Declaration?id=a0Oa000000MiWjWEAV
RoHS/RoHS3 Declarationhttps://www.globtek.com/pdf/rohs_cert/a0Oa000000MiWjWEAV
Prop 65 Statementhttps://www.globtek.com/r2/PH7CNf
REACH Declarationhttps://www.globtek.com/r2/eM2co8
Conflict Minerals Declarationhttps://www.globtek.com/r2/vZY8R5
Model Parameters
TypeEnclosed-Metal
TechnologyProgrammable Single Output Power Supply AC Adaptor
CategoryICT/ITE Power Supply
Input Voltage Range (V)90 ~ 264VAC, 127 ~ 370VDC (47 ~ 63Hz)
Max Input Current (A)9.3A / 115VAC, 3.7A / 230VAC
Max Output Power Rating (W)800
Output Voltage Range (V)12-60
EfficiencyN/A
Ingress ProtectionIPX0
Size (mm)127x41x249
EnclosureUser-added image

User-added image
User-added image
User-added image

User-added image

User-added image
User-added image
User-added image
User-added image
User-added image
 
Rating Table
Model Number (Final ordering #/Part No to be defined)Voltage (V)Current (A)Power (W)RFQ
GT-G3062P80012*1266.7800.4
GT-G3062P80015*1553.4801
GT-G3062P80024*2433.5804
GT-G3062P80030*3026.7801
GT-G3062P80036*3622.3802.8
GT-G3062P80048*4816.7801.6
GT-G3062P80060*6013.4804
* (Final ordering #/Part No to be defined)
Specifications
Features:
Universal AC input / Full range
Programmable output Voltage (0% ~ 105%)
Programmable output Current (0% ~ 105%)
Forced current sharing at parallel operation
Constant current limit
Selectable +5V / 0.5A or +9V / 0.3A auxiliary output
Global control via RS232
Remote setting multiple PSU via RS232, RS485 & I²C
Power OK signal
Remote ON / OFF, Remote sense function
Protection: OVP, OLP, OTP, Fan failure

Output
DC Voltage Range: 12V, 15V, 24V, 30V, 36V, 48V, 60V
Rated Current: 66.7A 53.4A 33.5A 26.7A 22.3A 16.7A 13.4A
Current Range: 0 ~ 66.7A 0 ~ 53.4A 0 ~ 33.5A 0 ~ 26.7A 0 ~ 22.3A 0 ~ 16.7A 0 ~ 13.4A
Rated Power: 800W 801W 804W 801W 802.8W 801.6W 804W
Ripple & Noise (Max.): 120mVp-p 150mVp-p 240mVp-p 300mVp-p 360mVp-p 480mVp-p 600mVp-p
Voltage Adj. Range: ±5.0% Typical adjustment by potentiometer. (VR1)
Voltage Tolerance: ±2.0%
Line Regulation: ±1.0%
Load Regulation: ±1.0%
Setup, Rise Time: 800ms, 100ms at full load
Hold Up Time (Typ.):14ms / 230VAC at full load

Input
Voltage Range: 90 ~ 264VAC, 127 ~ 370VDC
Frequency Range: 47 ~ 63Hz
Power Factor (Typ.):0.95 / 230VAC, 0.98 / 115VAC at full load
Efficiency (Typ.): 89% 90% 92% 92% 92% 92% 93%
AC Current (Typ.): 9.3A / 100VAC, 3.7A / 240VAC
Inrush Current (Typ.):30A / 115VAC, 60A / 230VAC
Leakage Current: < 1.0mA / 240VAC

Protection
Over Load: 105% rated output power, Protection type: Constant current limit
Over Voltage: Variable OVP, 120 ± 7% Vout. Refer to VCI VS OVP curve. Protection type: Latch-style (Recovery after reset AC power ON or inhibit)
Over Temperature: 85 ±5°C detect on NTC, Protection type: Auto recovery after temperature goes down

Function
Auxiliary Power: Selectable +5V / 0.5A or +9V / 0.3A auxiliary output
Remote ON / OFF Control: By external switch
Power OK Signal: Open drain signal low when PSU turns on, Max. sink current: 20mA, Max. drain voltage: 40V.
Output Voltage Trim: Adjustment of output voltage is between 0 ~ 105% of rated output
Output Current Trim: Adjustment of output current is between 0 ~ 105% of rated output
Parallel (Current Sharing): Note.5
Address Setting: Up to 8 units can be set using an address switch (sw1), 0~7

Environment
Working Temp.: -20 ~ +60°C (Refer to de-rating curve)
Working Humidity: 20 ~ 90% RH non-condensing
Storage Temp. & Humidity: -40 ~ +85°C, 10 ~ 95% RH
Temp. Coefficient: ±0.02% / °C (0 ~ 50°C)
Vibration: 10 ~ 500Hz, 2G 10min. / 1cycle, period for 60min. each along X, Y, Z axes Compliance to IEC 68-2-6, IEC 68-2-64

Safety & EMC
Safety Standards: Certified UL 60950-1; EN 60950-1
Withstand Voltage: I/P-O/P: 3KVAC (4242VDC), I/P-FG: 1.5KVAC (2121VDC), O/P-FG: 0.5KVAC (707VDC)
Isolation Resistance: I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
EMI Conduction & Radiation: Certified EN 55022; EN 61204-3; EN 61000-6-3
Harmonic Current: Certified EN 61000-3-2; EN 61000-3-3
EMS Immunity Certified: EN 55024; EN 61204-3; EN 61000-6-1; IEC 61000-4-2, 3, 4, 5, 6, 8, 11

Others
Cooling: Load and temperature control fan
Dimension (WxHxD) 127x41x249 mm / 5.000x1.614x9.803 inch
Packing: 1.7kg; 6pcs / 11.2kg / 0.55CUFT

Note
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uF & 47uF parallel capacitor.
3. Tolerance: includes setup time tolerance, line regulation and load regulation.
4. De-rating may apply in low input voltage. Please check the de-rating curve for more details.
5. In parallel connection only one unit will operate if the total output load is less than 5% of the rated power.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
7. This test done without enclosure.
Derating CurveUser-added image

 
Qty (ea.)/Carton6
Individual Box/Gift Box Size (mm)275*130*45
Individual Box/Gift Box ColorWhite
Master Carton Size (mm)TBD
Gross Weight (kg)11.2
Label Width (mm)116.0
Label Height (mm)30.0
Input Configuration
Description3 Positon Terminal Block
Optional Input Wiring Kits are available:
 
PN/Ordering NoLengthEnd AEnd B
C810070M6MLX5(R)60IEC 60320 C8 (Faston)MOLEX 09-50-3051
C810070M6MLX5HW(R)60IEC 60320 C8 (Hardwired)MOLEX 09-50-3051
C1410070M6MLX5(R)60IEC 60320 C13MOLEX 09-50-3051
MLX5410070M7MLX5(R73MOLEX 09-50-3051MOLEX 09-50-3051
Custom lengths, construction, cable types, ferrites, filters, and termination available upon request.
 
Approvals

Below follows a link to the latest regulatory certifications and marks for this specific product. National standards as well as certification schemes are constantly changing and so is the set of certification marks and symbols applicable to this product. Various standards, marks and symbols, and certificates are subject to change at any time without notice.

Additional standards or unique country certifications are available upon request. Please contact Globtek to request a quotation.

LogoDescription
User-added image
 
GOST-R mark for Russia(Document: http://www.globtek.com/html/iso_certificates/GT_GOST-R.pdf). 03/15/2015. Due to lack of demand, GlobTek will not be renewing it's GOST certification. Please contact your sales engineer for pricing on EAC.
User-added imageIndoor Use Only - Mark is on the label or Molded in the case
User-added imageUL60950-1, cULus to UL 60950-1 E170507
User-added imageJAPAN TUV Rheinland-PSE GlobTek Inc to J60950-1(H26) , J55022(H22),J3000(H25).Please follow the procedure listed in the following link for proper import to Japan: https://www.globtek.com/r2/Szj4Vb
User-added imageCHINA SJ/T 11364-2014, China RoHS Chart: http://www.globtek.com/pdf/F-GT-DJD-8.4.1-006%20China%20RoHS%20Declaration%205-20-22.pdf
User-added imageUKCA Certification
User-added imageAttention Mark / Refer to operating manual for operating and service instructions
User-added imageUkraine UKRSepro (Document: www.globtek.com/html/iso_certificates/GT_Ukraine.pdf)

User-added image  
CE Certification
RoHSSpecifications of directive 2011/65/EU Annex VI (ROHS-2) with amendment 2015/863-EU (ROHS-3) http://www.ce-mark.com/Rohs%20final.pdf
 User-added imageWEEE: Complies with EU 2012/19/EU (http://ec.europa.eu/environment/waste/weee/index_en.htm) Mark is on the label or Molded in the case
nullClass I Earth Ground
User-added imageJapan: Voluntary Control Council for Interference (VCCI)
Request Info